XM3.1-915-HP
Power Supply
 
 

Alarms
 

Battery
 

Power Supply
Model ALPHA/XM3.1-915-HP
Firmware V1.01.0
Major Alarm OK
Minor Alarm OK
Operational Mode Line
Charger Mode Float
Tamper Closed
Power Supply Language English
Power Supply Priority Normal
Input
AC Line Mode OK
Voltage 122.20 V
Current 3.13 A
Power 300 W
Frequency 60 Hz
Tap Status Normal
Frequency Range 3.00 Hz
Current Limit 17.00 A
Input Power Consumption 369 Wh
Output
Voltage 87.78 V
Power 165 W
Apparent Power 212.42 VA
Frequency 60.07 Hz
Percent Load 16.10 %
Output Setting 90 V
Output Regulation Coarse override
Over-current Tolerance 3.000 sec
Retry Delay 60 sec
Retry Limit 20
Active Drop Alarm OK
Active Drop Threshold 50 W
Current 2.42 A
Inverter
Inverter Status Off
End of Discharge Type String
End of Discharge Level 1.75 V/cell
Reduced Peak Mode Disable
Total Standby Events 86
Time Since Last Standby Event 120d 2h:15m
Time in Last Standby Event 0d 0h:07m
Total Time in Standby 321 min
Standby Events Since Reset 39
Time in Standby Since Reset 13 min
Time Since Reset 842 day(s)
Total Run Time 842 day(s)
Transformer Run Time 842 day(s)
Total Downtime 0d 0h:01m
Oil Cap Lifespan Consumed 34.3 %
Self Test
Deep Discharge Cycle Timed
Test Countdown 25 day(s)
Test Duration 10 min
Test Interval 30 day(s)
Test Inhibit No

 